Dimensions

<< Click to Display Table of Contents >>

Navigation:  Impeller > Main dimensions > Centrifugal, Mixed-flow Pump/ Fan >

Dimensions

Previous pageReturn to chapter overviewNext page

In the panel Shaft, the required shaft diameter is computed.
¢ Shaft/ Hub

The hub diameter is determined by the user and depends on the shaft-hub connection.

The main dimensions can be seen on Main dimensions panel. They can be recomputed by pressing the Calculate-button. The computation is based on "Euler's Equation of Turbomachinery", on the continuity equation and the relations for the velocity triangles as well as on the parameters given in the tab sheets Setup and Parameters.

Individual main dimensions can be calculated separately using the button inside the value field.

You may accept the proposed values or you can modify them slightly, e.g. to meet a certain normalized diameter.

In case the checkbox Automatic is activated a new calculation will accomplished after any change of parameter. Then the manual alteration of the main dimensions is not possible.

Due to the Euler equation the impeller diameter d2 and the blade angles βB2 are coupled (see Outlet triangle). Lower d2 values result in higher βB2 (higher blade loading) and vice versa. For that reason the resulting average βB2 value is displayed for information right beside the calculated/ specified d2 value.

You can select a value for the diameters dS from standard specifications. For that purpose you have to press the settings button right beside the input field.

The small dialog gives you the possibility to select a diameter from several standard specifications. If material, standard name and pressure range are selected the lower panel shows all diameters of the chosen standard. One diameter is highlighted as a proposal. Nominal diameter, outside diameter and wall thickness for the marked entry is displayed. Using of and buttons additional standard specifications and user defined diameters can be added or existing parameters can be removed from the list.

At File location the name of the file containing the diameters is shown. The file is originally called Diameter.cftdi and is located in the installation directory of CFturbo. Modifications of the list will be saved if the user is leaving the dialog window by clicking the OK-button. In case there are no write permissions the user can choose another directory to save the file. Renaming of files is possible by Save as- functionality. By clicking the Open-button a previously saved file can be opened.

 

Neighboring components

In specific cases the dimensions of the neighboring components at inlet and/ or outlet can be used to get exactly matching geometry.

This feature is available only for explicitly uncoupled components or side-by-side impellers.

Information

In the right panel of any tab sheet an information panel is situated, which holds the computed variables in accordance to the actual state of design, the resulting Meridional section as well as the Cordier-Diagramm with the location of the best point. These three sections can be chosen by the appropriate soft buttons in the heading.

In the Value section the following variables are displayed for information which result from calculated or determined main dimensions:

Flow properties at:
- impeller inlet
- impeller outlet

static pressure p
total pressure pt
volume flow Q
mass flow
swirl s

Velocity triangles at:
- impeller inlet
- impeller outlet

velocities u, cm, cm*, cu, c, wu, w
flow angles α, β

Work coefficient

Flow coefficient

Meridional flow coefficient

Specific diameter

Inlet velocity

Inlet velocity (net)

Outlet velocity

Outlet velocity (net)

Outlet width ratio

Meridional deceleration

Estimated axial force

Reynolds number

with d1 = highest diameter at inlet

with b1 = width at inlet

with d2 = highest diameter at outlet

with b2 = width at outlet

NPSHR estimation
(Pumps only)

(Available at inlet)

Available head level distance to vaporization at impeller inlet (pv = fluid vapor pressure)

Lobanoff/ Ross

see diagram below this table

Pfleiderer


 
with loss coefficients
λc = 1.1 … 1.35, λw = (0.03) 0.1 … 0.3

Gülich


or

 
with suction specific speed nSS = 160…280

Stepanoff


 
with cavitation number σ = 1.22 ∙10-3 ∙nq4/3

Petermann


 
with suction number Sq = (0.2) 0.4…0.6 (2.0)

Europump

NPSHR prediction
according to
Lobanoff/ Ross

 

The Meridional preview is until now based on the main dimensions only.

 

The Cordier diagram can be used for checking the impeller diameter d2.

See Cordier.

The Velocity triangles are the result of a mid-span calculation and are based on the design point and the main dimensions.

Possible warnings

Problem

Possible solutions

Use of dS/d2 requires dH=0.

This applies for fans only. If the suction diameter dS is calculated by diameter ratio dS/d2, then the hub has to be planar, i.e. hub diameter dH = 0. Otherwise the empirical correlations are invalid.

Select a different parameter for the calculation of the suction diameter dS (see Parameters).

Inlet/ Outlet: Pressure and temperature not within the liquid phase of the fluid.
Check inlet condition and geometry.

If the fluid model = CoolProp, fluid properties will be calculated as function of pressure and temperature. In case the local pressure and temperature are not above the vapor pressure curve, the fluid state is not valid.

Increase main dimensions (width, diameter etc.) or change Global setup (e.g., decrease mass flow, increase pressure, decrease temperature).